0
  • DE
  • EN
  • FR
  • International Database and Gallery of Structures

Advertisement

Heat pumps on exhaust air for space heating and domestic hot water, in very high energy performance multifamily building (Geneva, Switzerland): feedback in actual condition of use

Author(s):

Medium: journal article
Language(s): English
Published in: Journal of Physics: Conference Series, , n. 2, v. 2600
Page(s): 022019
DOI: 10.1088/1742-6596/2600/2/022019
Abstract:

This paper, which is based on a monitored case study, analyses the issues and potential of heat recovery on exhaust air in new multi-family buildings, for combined DHW and SH production by way of heat pumps, in combination with a gas boiler for peak loads. Analysis of the hydraulic diagram, as well as readings of heat and energy meters, allows to point out the causes of an actual HP share (38%) much lower than the projected value (61%), while bringing up the necessity to elaborate standard schemes and sizing rules for such systems.

Copyright: © 2023 S Callegari, P Hollmuller
License:

This creative work has been published under the Creative Commons Attribution 3.0 Unported (CC-BY 3.0) license which allows copying, and redistribution as well as adaptation of the original work provided appropriate credit is given to the original author and the conditions of the license are met.