Heat pumps on exhaust air for space heating and domestic hot water, in very high energy performance multifamily building (Geneva, Switzerland): feedback in actual condition of use
Autor(en): |
S. Callegari
P. Hollmuller |
---|---|
Medium: | Fachartikel |
Sprache(n): | Englisch |
Veröffentlicht in: | Journal of Physics: Conference Series, 1 November 2023, n. 2, v. 2600 |
Seite(n): | 022019 |
DOI: | 10.1088/1742-6596/2600/2/022019 |
Abstrakt: |
This paper, which is based on a monitored case study, analyses the issues and potential of heat recovery on exhaust air in new multi-family buildings, for combined DHW and SH production by way of heat pumps, in combination with a gas boiler for peak loads. Analysis of the hydraulic diagram, as well as readings of heat and energy meters, allows to point out the causes of an actual HP share (38%) much lower than the projected value (61%), while bringing up the necessity to elaborate standard schemes and sizing rules for such systems. |
Copyright: | © 2023 S Callegari, P Hollmuller |
Lizenz: | Dieses Werk wurde unter der Creative-Commons-Lizenz Namensnennung 3.0 (CC-BY 3.0) veröffentlicht und darf unter den Lizenzbedinungen vervielfältigt, verbreitet, öffentlich zugänglich gemacht, sowie abgewandelt und bearbeitet werden. Dabei muss der Urheber bzw. Rechteinhaber genannt und die Lizenzbedingungen eingehalten werden. |
0.64 MB
- Über diese
Datenseite - Reference-ID
10777749 - Veröffentlicht am:
12.05.2024 - Geändert am:
05.06.2024