Vibration Test and Control of Factory a Building under Excitation of Multiple Vibrating Screens
Author(s): |
Jianxin Yu
Zhenzhen Li Zhenhua Zhang Wusheng Zhao Zhiwei Niu Jingji Cheng |
---|---|
Medium: | journal article |
Language(s): | English |
Published in: | Buildings, 24 April 2022, n. 5, v. 12 |
Page(s): | 607 |
DOI: | 10.3390/buildings12050607 |
Abstract: |
In order to reduce the excessive vibration responses of a reinforced concrete frame structure induced by several vibrating screens working simultaneously, field vibration monitoring and some vibration reduction measures are carried out. The results of field vibration monitoring show that the maximum vertical vibration of the structure exceeds 106% of the limitation of building vibration. The results of the structural response analysis show that the excessive structural vibration is attributed to the resonance, as the frequency of the vibrating screens coincides with vertical natural frequency of the floors of the factory structure. Based on this fact, three vibration control measures, including damping, active vibration isolation of vibrating screens and structural vibration absorption, are proposed to mitigate the excessive vibration. In order to analyze the vibration control performance of the proposed schemes, the finite element dynamic model of the factory building structure is established, and the model is verified by the results of vibration and mode tests. Then, the damping system, vibration isolation system and vibration absorption system are set up in the models, and the vibration control performance of the three schemes are investigated. The results show that the measures, including vibration isolation and absorption, can reduce the vibration by more than 80%. Combined with the demand for a short construction period, the active vibration isolation of vibrating screens is finally selected. After the implementation of the scheme, the field monitoring data show that the structural vibration response is consistent with the finite element result and obviously weakened to meet the limitation. This study can provide a reference for the vibration control design for similar screening factory buildings. |
Copyright: | © 2022 by the authors; licensee MDPI, Basel, Switzerland. |
License: | This creative work has been published under the Creative Commons Attribution 4.0 International (CC-BY 4.0) license which allows copying, and redistribution as well as adaptation of the original work provided appropriate credit is given to the original author and the conditions of the license are met. |
6.9 MB
- About this
data sheet - Reference-ID
10679415 - Published on:
18/06/2022 - Last updated on:
10/11/2022