Measurement and rapid assessment of indoor air quality at mass gathering events to assess ventilation performance and reduce aerosol transmission of SARS-CoV-2
Author(s): |
Liora Malki-Epshtein
Filipa Adzic Ben M. Roberts Elizabeth Abigail Hathway Christopher Iddon Murat Mustafa Malcolm Cook |
---|---|
Medium: | journal article |
Language(s): | English |
Published in: | Building Services Engineering Research and Technology, 13 December 2022, n. 2, v. 44 |
Page(s): | 113-133 |
DOI: | 10.1177/01436244221137995 |
Abstract: |
To assess risk factors for COVID-19 transmission and address the closure of mass gathering events since March 2020, the UK Government ran the Events Research Programme (ERP), following which it reopened live events in sports, music, and culture in July 2021. We report the rapid post-occupancy evaluation of Indoor Air Quality (IAQ) and associated long-range airborne transmission risk conducted in the Environmental Study of the ERP. Ten large venues around the UK were monitored with CO2 sensors at a high spatial and temporal resolution during 90 events. An IAQ Index based on CO2 concentration was developed, and all monitored spaces were classified in bands from A to G based on their average and maximum CO2 concentrations from all events. High resolution monitoring and the IAQ Index depicted the overall state of ventilation at live events, and allowed identification of issues with ventilation effectiveness and distribution, and of spaces with poor ventilation and the settings in which long-range airborne transmission risk may be increased. In numerous settings, CO2 concentrations were found to follow patterns relating to event management and specific occupancy of spaces around the venues. Good ventilation was observed in 90% of spaces monitored for given occupancies. Practical applications: High-resolution monitoring of indoor CO2 concentrations is necessary to detect the spatial variation of indoor air quality (IAQ) in large mass gathering event venues. The paper summarises COVID-19 ventilation guidance for buildings and defines a methodology for measurement and rapid assessment of IAQ during occupancy at live events that can be implemented by venue managers. Comparisons of the CO2 concentrations measured during the events identified the spaces at high risk of long-range transmission of airborne pathogens. Building operators should be mindful of the ventilation strategies used relative to the total occupancy in different spaces and the occupant’s activities. |
- About this
data sheet - Reference-ID
10714227 - Published on:
21/03/2023 - Last updated on:
21/03/2023