Flexural Behaviour of a Cold-Formed Steel-Concrete Composite Beam with Channel Type Shear Connector – An Experimental and Analytical Study
Author(s): |
Sangeetha Palanivelu
(SSN College of Engineering , Chennai , India)
|
---|---|
Medium: | journal article |
Language(s): | English |
Published in: | Civil and Environmental Engineering Reports, September 2019, n. 3, v. 29 |
Page(s): | 228-240 |
DOI: | 10.2478/ceer-2019-0038 |
Abstract: |
Steel-concrete composite structures are widely used in the current construction of bridges and multi-storey buildings. The effect of shear connectors in a cold-formed steel-composite beam was studied under flexure. The number of channel connectors in the specimen was varied and the same was compared with a specimen without shear connectors. The performance and failure of cold-formed steel-composite beams were then studied. The presence of shear connectors in the tension zone prevents the formation of cracks which are the major cause of failure in a beam subjected to bending. The load-carrying capacity is greater in a composite beam and an increase in the number of channel connectors from one to five increases the load-carrying capacity by 60 % as compared to a specimen without a connector. A composite beam with five connectors is more ductile, with a ductility factor of 14. The Composite beams were also analysed using the finite element software ANSYS and were found to have good agreement with the experimental results. |