Field Study on Impact of Mechanical Pressurization on Pressure Distribution in High-Rise Buildings

Author(s):
ORCID

Medium: journal article
Language(s): English
Published in: Buildings, , n. 12, v. 13
Page(s): 3039
DOI: 10.3390/buildings13123039
Abstract:

In high-rise buildings, the excessive pressure differences cause various problems, and architectural and mechanical measures are always applied. In this study, pressure measurements on a 67-story high-rise building were conducted to evaluate the effect of mechanical pressurization on the pressure distribution. Absolute pressure measurement devices were installed at 28 points on 10 floors, a full-scale pressure profile of the test building was derived, and the pressure distributions on the main floors were reviewed. Four pressurization modes for the test building were considered, and the variation in the pressure distribution for each mode was analyzed. The results showed that mechanical pressurization reduced the pressure difference on the lobby floor by approximately 18%. Although it did not exert an apparent impact on the pressure difference due to the stack effect, pressurizing the entire floor serves as the most effective way of reducing the excessive pressure difference.

Copyright: © 2023 by the authors; licensee MDPI, Basel, Switzerland.
License:

This creative work has been published under the Creative Commons Attribution 4.0 International (CC-BY 4.0) license which allows copying, and redistribution as well as adaptation of the original work provided appropriate credit is given to the original author and the conditions of the license are met.

  • About this
    data sheet
  • Reference-ID
    10754329
  • Published on:
    14/01/2024
  • Last updated on:
    07/02/2024
 
Structurae cooperates with
International Association for Bridge and Structural Engineering (IABSE)
e-mosty Magazine
e-BrIM Magazine