0
  • DE
  • EN
  • FR
  • International Database and Gallery of Structures

Advertisement

Cooling Tower Plume and Drift Concentration in presence of Urban Canyon

Author(s):


Medium: journal article
Language(s): English
Published in: IOP Conference Series: Earth and Environmental Science, , n. 1, v. 1279
Page(s): 012028
DOI: 10.1088/1755-1315/1279/1/012028
Abstract:

This paper presents a computational analysis of the cooling tower plume and drift emitted by mechanical draught cooling towers situated in urban areas. The data from the Wang X (2019) and Briggs plume lift height formula are used to prove results obtained from computational Modeling of cooling tower drift and it was found to be effective. The simulation setup uses a multiphase mixture model for plume analysis and DPM for analysis of drift in the Ansys fluent. The CFD simulation results are accurate within 50 to 100 m with the Briggs plume lift height formula. The effect of wind coming from urban canyons on the cooling tower results in decreased plume lift height and increase drift concentration and deposition rate on the ground.

Structurae cannot make the full text of this publication available at this time. The full text can be accessed through the publisher via the DOI: 10.1088/1755-1315/1279/1/012028.