The Collapse Analysis of A Transmission Tower Under Wind Excitation
Author(s): |
Li Tian
Qiqi Yu Ruisheng Ma Chengwu Wang |
---|---|
Medium: | journal article |
Language(s): | English |
Published in: | The Open Civil Engineering Journal, June 2015, n. 1, v. 8 |
Page(s): | 136-142 |
DOI: | 10.2174/1874149501408010136 |
Abstract: |
The collapse of a transmission tower under wind action is studied in this paper. A three-dimensional finite element model of the transmission tower is established based on a real project. The birth-to-death element technique is adopted in ABAQUS/Explicit. Kaimal fluctuating wind power spectrum and the harmony superposition method are used to simulate the fluctuating wind speed time history. The dynamic behavior and the collapse mechanism of the transmission tower under three different angles of attack α = 0o, 45oand 90oare carried out, respectively. The results show that the collapse of the transmission tower at 45oangle of attack occurs easily, but it is contrary at 90oangle of attack. The fracture position of the transmission tower under wind excitation is obtained, and the initial damage of the members happens simultaneously in the main and the secondary element. The results of the collapse analysis can provide reference to the design of the transmission tower and the reinforcement of this structure to prevent the collapse of the tower. |
Copyright: | © 2015 Li Tian et al. |
License: | This creative work has been published under the Creative Commons Attribution 4.0 International (CC-BY 4.0) license which allows copying, and redistribution as well as adaptation of the original work provided appropriate credit is given to the original author and the conditions of the license are met. |
1.44 MB
- About this
data sheet - Reference-ID
10175730 - Published on:
02/01/2019 - Last updated on:
02/06/2021