The Collapse Accident Analysis for Steel Structure of Waste-heat Boiler in a Cement Plant
Author(s): |
Zaihua Zhang
Xingping Shu Zhishen Yuan Ran He |
---|---|
Medium: | journal article |
Language(s): | English |
Published in: | The Open Civil Engineering Journal, March 2016, n. 1, v. 9 |
Page(s): | 82-89 |
DOI: | 10.2174/1874149501509010082 |
Abstract: |
By means of on-siteinvestigation, inspection,interior experiments, theoreticalanalysis and calculation, a detailed analysisis carried out on the causeof the partialcollapse accident about a waste-heat boiler steel structure in a cement plant of Hunan province of China. The resultsof inspectionand analysis show that: as a key part of load transfer, the connection weld of long thin steel plate is poor in quality, meanwhile, the detail of beam-column connection can not meet the requirement of rigid joint stipulated by the design, which are the main causes for the collapse accident of boiler steel structure. Based on the analysis of accident cause, some problems worthy of consideration are put forward to the design and constructionof this kind of structure, such asthe weld procedure and quality control of long thin steel plate connection weld, etc. |
Copyright: | © 2016 Zaihua Zhang et al. |
License: | This creative work has been published under the Creative Commons Attribution 4.0 International (CC-BY 4.0) license which allows copying, and redistribution as well as adaptation of the original work provided appropriate credit is given to the original author and the conditions of the license are met. |
0.93 MB
- About this
data sheet - Reference-ID
10175651 - Published on:
30/12/2018 - Last updated on:
02/06/2021