Seismic Protection of the Eskişehir City Hospital in Turkey

 Seismic Protection of the Eskişehir City Hospital in Turkey
Author(s): , ,
Presented at IABSE Symposium: Engineering the Future, Vancouver, Canada, 21-23 September 2017, published in , pp. 2219-2225
DOI: 10.2749/vancouver.2017.2219
Price: € 25.00 incl. VAT for PDF document  
ADD TO CART
Download preview file (PDF) 0.35 MB

The Eskişehir City Hospital with four main building blocks is located 250 km south east of Istanbul in a rather highly seismic zone of Turkey with up to 0,6 g PGA. To avoid any fatalities or damage...
Read more

Bibliographic Details

Author(s): (MAURER SE, Munich, BY, Germany)
(MAURER SE, Munich, BY, Germany)
(MAURER SE, Munich, BY, Germany)
Medium: conference paper
Language(s): English
Conference: IABSE Symposium: Engineering the Future, Vancouver, Canada, 21-23 September 2017
Published in:
Page(s): 2219-2225 Total no. of pages: 7
Page(s): 2219-2225
Total no. of pages: 7
Year: 2017
DOI: 10.2749/vancouver.2017.2219
Abstract:

The Eskişehir City Hospital with four main building blocks is located 250 km south east of Istanbul in a rather highly seismic zone of Turkey with up to 0,6 g PGA. To avoid any fatalities or damages to the structure and enable absolute continued functionality even after the MCE event, it was decided to apply seismic isolation with pendulum isolators.

This paper will show the design considerations to limit the base shear within the isolated building blocks for the MCE event down to less than 0.13 W (W = seismic weight = Dead Load + 0.3 Live Load) on isolator top level and max. 0.2 W on the upper floor building levels of the structure and the realization with suitable seismic pendulum isolators.

For these low shear level requirements the isolator performance was adjusted to 3.5 s effective period and 26 % damping.

Keywords:
isolation earthquake protection low base shear no damages pendulum isolator