Thermal Performance Investigation at Different Temperature and Airflow Settings in a Conference Hall of Expo Building

Auteur(s): ORCID
ORCID


Médium: article de revue
Langue(s): anglais
Publié dans: Buildings, , n. 9, v. 12
Page(s): 1418
DOI: 10.3390/buildings12091418
Abstrait:

The airflow distribution for a large space, such as a conference hall, is quite challenging to achieve a good and uniform thermal distribution. In the recent study, insufficient quantitative knowledge has been provided, notably for the appropriate supply air temperature and air velocity for the conference hall environment. In this study, a full-scale conference hall was simulated extensively for an expo building in Taiwan. A total of nine experiment numbers were carried out with various supply air temperature and air velocity settings. Through the use of a CFD approach, this study seeks to identify the ideal parameters for a comfortable and acceptable airflow distribution and temperature, with an eye toward potential compromises with an energy-efficient approach. The results demonstrate that the temperature distribution ranges from 18 to 26 °C, indicating an acceptable indoor thermal environment, depending on the parameter settings. The best settings for providing a pleasant indoor thermal environment are with a supply air temperature and air velocity of 15 °C and 1 m/s, which can keep the PMV index between −0.5 and 0.5. Utilizing a greater temperature setting may save energy, but sufficient air velocity must be addressed in order to meet the indoor thermal conditions. Furthermore, a greater air velocity may generate more noise and disrupt the situation in the conference hall, so it must be selected specifically.

Copyright: © 2022 by the authors; licensee MDPI, Basel, Switzerland.
License:

Cette oeuvre a été publiée sous la license Creative Commons Attribution 4.0 (CC-BY 4.0). Il est autorisé de partager et adapter l'oeuvre tant que l'auteur est crédité et la license est indiquée (avec le lien ci-dessus). Vous devez aussi indiquer si des changements on été fait vis-à-vis de l'original.

  • Informations
    sur cette fiche
  • Reference-ID
    10692576
  • Publié(e) le:
    23.09.2022
  • Modifié(e) le:
    10.11.2022
 
Structurae coopère avec
International Association for Bridge and Structural Engineering (IABSE)
e-mosty Magazine
e-BrIM Magazine