Thermal Environment Analysis and Optimization for Large Space Buildings with Radiant Cooling Floors: A Case Study of Xianyang International Airport
Auteur(s): |
Rong Hu
Haolin Wang Junqi Liang Xiaoping Li Wenheng Zheng Gang Liu |
---|---|
Médium: | article de revue |
Langue(s): | anglais |
Publié dans: | Buildings, 24 avril 2024, n. 5, v. 14 |
Page(s): | 1355 |
DOI: | 10.3390/buildings14051355 |
Abstrait: |
Radiant cooling floors combined with ventilation systems have been widely applied in large space buildings. However, there has been a lack of research on system control strategies for their adaptation to weather changes. This study aimed to find control strategies for radiant cooling floors combined with displacement ventilation systems used in large space buildings in order to achieve energy conservation and environmental improvement. Supply air temperature and cooling surface temperature were determined to be the control variables. It was found that cooling capacity of the combined system and the comfort index, PMV (predicted mean vote), were linear in relation to the supply air temperature and cooling surface temperature. The linear equations regarding cooling capacity and PMV were established separately using environment data, and then the optimal region was determined. A case study on Terminal 3 of Xi’an Xianyang International Airport was conducted. The thermal environment was investigated through on-site measurements, questionnaires, and numerical simulations with CFD (computational fluid dynamics). It was found that supply air temperature and cooling surface temperature had a significant impact on PMV, and less impact on the cooling capacity. Therefore, it was determined that the supply air temperature should be altered first when the indoor temperature exceeds the upper limit, and then the cooling surface temperature should be changed if the indoor environment continues to overheat with the supply air temperature set to 18 °C. Thus, the supply air temperature was kept at 18 °C, and the floor surface temperature was set to be 22 °C on a high-temperature day. The average PMV was 0.87, and the cooling capacity of the combined system was 200 W/(m2·K), according to the CFD simulation. In addition, the surface heat transfer coefficient of the cooling floor was found to be 10.26 W/(m2·K). This research provides important references for the design and operational management of radiant cooling floors in large space buildings. |
Copyright: | © 2024 by the authors; licensee MDPI, Basel, Switzerland. |
License: | Cette oeuvre a été publiée sous la license Creative Commons Attribution 4.0 (CC-BY 4.0). Il est autorisé de partager et adapter l'oeuvre tant que l'auteur est crédité et la license est indiquée (avec le lien ci-dessus). Vous devez aussi indiquer si des changements on été fait vis-à-vis de l'original. |
45.45 MB
- Informations
sur cette fiche - Reference-ID
10787473 - Publié(e) le:
20.06.2024 - Modifié(e) le:
20.06.2024