Abstrait: |
A full-scale model was established by the Fire Dynamics Simulator (FDS) to study the fire characteristics in the cable cabin of utility tunnel with different longitudinal fire source locations. Five fire sources at different locations were placed in a 200-meter-long fire compartment. Several important parameters were obtained and analyzed, including temperature distribution, smoke concentration, and fire self-extinguishing. The results present that the fire source located at 1/2 of the longitudinal direction has the largest range of high-temperature smoke, which leads to the largest damage range of the concrete structure. The reverse filling of the smoke in the utility tunnel leads to the longitudinal CO peak concentration first decreasing and then increasing from the fire source to the end. When the fire source is located at 1/8 of the longitudinal direction, the fire self-extinguishing time is the longest. These encouraging results could provide significant references for the fire protection design and fire control of the utility tunnel. |
License: | Cette oeuvre a été publiée sous la license Creative Commons Attribution 3.0 (CC-BY 3.0). Il est autorisé de partager et adapter l'oeuvre tant que l'auteur est crédité et la license est indiquée. |
1.4 MB
- Informations
sur cette fiche - Reference-ID
10780717 - Publié(e) le:
12.05.2024 - Modifié(e) le:
12.05.2024