Improvement of Fire Safety Performance for Nursing Homes by Using Fireproof Curtains with a Water Film System
Auteur(s): |
Su-Hua Chiu
Charlene Wu Chen-Yu Chen Ta-Hui Lin Shin-Ku Lee |
---|---|
Médium: | article de revue |
Langue(s): | anglais |
Publié dans: | Buildings, 20 septembre 2022, n. 10, v. 12 |
Page(s): | 1590 |
DOI: | 10.3390/buildings12101590 |
Abstrait: |
Nursing home residents often have impaired faculties, which limit their evacuation responses in light of accidents. Specifically, fire accidents can pose significant risks to both residents and property. In this study, we designed a water film cooling system to enhance the heat and smoke resistance of a fire retardant curtain without a fire resistance rating. The experimental results on a full-scale door/wall refractory furnace and smoke-barrier system showed that the proposed curtain had 1.5-h heat resistance properties, while the smoke control performance could meet the ISO 5925-1 requirement. Finally, we used Fire Dynamics Simulator (FDS) 6.0 to simulate an existing nursing home with this type of fireproof curtain setup for horizontal evacuation waiting space. The results show that our proposed water film cooling system can effectively inhibit the diffusion of smoke during the initial stage of a fire, creating a safe evacuation waiting zone for disadvantaged evacuees. |
Copyright: | © 2022 by the authors; licensee MDPI, Basel, Switzerland. |
License: | Cette oeuvre a été publiée sous la license Creative Commons Attribution 4.0 (CC-BY 4.0). Il est autorisé de partager et adapter l'oeuvre tant que l'auteur est crédité et la license est indiquée (avec le lien ci-dessus). Vous devez aussi indiquer si des changements on été fait vis-à-vis de l'original. |
8.37 MB
- Informations
sur cette fiche - Reference-ID
10700390 - Publié(e) le:
11.12.2022 - Modifié(e) le:
15.02.2023