Experimental Evaluation of the Ventilation Effectiveness of Corner Stratum Ventilation in an Office Environment
Auteur(s): |
Arman Ameen
Gasper Choonya Mathias Cehlin |
---|---|
Médium: | article de revue |
Langue(s): | anglais |
Publié dans: | Buildings, juillet 2019, n. 7, v. 9 |
Page(s): | 169 |
DOI: | 10.3390/buildings9070169 |
Abstrait: |
An experimental study was conducted in a room resembling an office in a laboratory environment. The study involved investigating the ability of corner-placed stratum ventilation in order to evaluate the ventilation’s effectiveness and local thermal comfort. At fixed positions, the air temperature, air velocity, turbulence intensity, and tracer gas decay measurements were carried out. The results show that corner-placed stratum ventilation behaves very similar to a mixing ventilation system when considering air change effectiveness. The performance of the system was better at lower supply air flow rates for heat removal effectiveness. For the heating cases, the draught rates were all very low, with the maximum measured value of 12%. However, for the cooling cases, the maximum draught rate was 20% and occurred at ankle level in the middle of the room. |
Copyright: | © 2019 by the authors; licensee MDPI, Basel, Switzerland. |
License: | Cette oeuvre a été publiée sous la license Creative Commons Attribution 4.0 (CC-BY 4.0). Il est autorisé de partager et adapter l'oeuvre tant que l'auteur est crédité et la license est indiquée (avec le lien ci-dessus). Vous devez aussi indiquer si des changements on été fait vis-à-vis de l'original. |