Comparative Study on Heat Dissipation Performance of Pure Immersion and Immersion Jet Liquid Cooling System for Single Server

Auteur(s):
ORCID
ORCID



Médium: article de revue
Langue(s): anglais
Publié dans: Buildings, , n. 9, v. 14
Page(s): 2635
DOI: 10.3390/buildings14092635
Abstrait:

Heat dissipation has emerged as a critical challenge in server cooling due to the escalating number of servers within data centers. The potential of immersion jet technology to be applied in large-scale data center server operations remains unexplored. This paper introduces an innovative immersion jet liquid cooling system. The primary objective is to investigate the synergistic integration of immersion liquid cooling and jet cooling to enhance the heat dissipation capacity of server liquid cooling systems. By constructing a single-server liquid cooling test bench, this study compares the heat dissipation efficiencies of pure immersion and immersion jet liquid cooling systems and examines the impact of inlet water temperature, jet distance, and inlet water flow rate on system performance. The experimental outcomes show that the steady-state surface heat transfer coefficient of the immersion jet liquid cooling system is 2.6 times that of the pure immersion system, with increases of approximately 475.9 W/(m2·K) and 1745.0 W/(m2·K) upon adjustment of the jet distance and flow rate, respectively. Furthermore, the system model is streamlined through dimensional analysis, yielding a dimensionless relationship that encompasses parameters such as inlet water temperature, jet distance, and inlet water velocity. The correlation error is maintained below 18%, thereby enhancing the comprehension of the immersion jet cooling mechanism.

Copyright: © 2024 by the authors; licensee MDPI, Basel, Switzerland.
License:

Cette oeuvre a été publiée sous la license Creative Commons Attribution 4.0 (CC-BY 4.0). Il est autorisé de partager et adapter l'oeuvre tant que l'auteur est crédité et la license est indiquée (avec le lien ci-dessus). Vous devez aussi indiquer si des changements on été fait vis-à-vis de l'original.

  • Informations
    sur cette fiche
  • Reference-ID
    10795052
  • Publié(e) le:
    01.09.2024
  • Modifié(e) le:
    01.09.2024
 
Structurae coopère avec
International Association for Bridge and Structural Engineering (IABSE)
e-mosty Magazine
e-BrIM Magazine