Full-scaled experiment on flexural behavior of pre-tensioned prestressed bulb T-beam
|
Bibliografische Angaben
Autor(en): |
Bowen Feng
(Chang’an University, Xi’an, China)
Yongjian Liu (Chang’an University, Xi’an, China) |
||||
---|---|---|---|---|---|
Medium: | Tagungsbeitrag | ||||
Sprache(n): | Englisch | ||||
Tagung: | IABSE Congress: Resilient technologies for sustainable infrastructure, Christchurch, New Zealand, 3-5 February 2021 | ||||
Veröffentlicht in: | IABSE Congress Christchurch 2020 | ||||
|
|||||
Seite(n): | 172-179 | ||||
Anzahl der Seiten (im PDF): | 8 | ||||
DOI: | 10.2749/christchurch.2021.0172 | ||||
Abstrakt: |
In order to study the flexural behavior of bulb T-beam, a full-scaled specimen was test until failure. The prestress friction loss, load-displacement relationship, crack distribution and failure mode of the specimen were measured. It showed that obvious friction existed between plate-type bend device using 16Mn and steel strand and the frictional coefficient equals 0.25. The failure mode of the test beam conformed to the design criterion of balanced-reinforced beam. Additionally, the test results were compared to the results calculated by guidelines including JTJ 3362-2018, GB 50010- 2010, ACI 318m-14 and Eurocode 2. It showed that all the guidelines could accurately predict the cracking moment, but overestimate the ultimate flexural capacity. Eurocode 2 and JTG 3362-2018 could accurately determine the deformation and crack width, respectively. |