Simulation and Comparative Analysis on Environmental Control in Subway
Autor(en): |
Ming Liu
Bao Gang Zhang Liu Wen Zhong Zhi Huang |
---|---|
Medium: | Tagungsbeitrag |
Sprache(n): | Englisch |
Tagung: | 2012 International Conference on Civil, Architectural and Hydraulic Engineering (ICCAHE 2012), August 10-12th 2012, Zhangjiajie (China) |
Veröffentlicht in: | Sustainable Cities Development and Environment [3 vols] |
Seite(n): | 1068-1072 |
DOI: | 10.4028/www.scientific.net/AMM.209-211.1068 |
Abstrakt: |
To ensure passengers can have a comfortable thermal environment in the subway waiting room is one of the main targets in subway environment control. By using the CFD software, this paper takes an island platform with double-layer of Shenyang as the object to simulate the thermal environment of platform screen door and ventilation in the open system, then detailed analysis on the variation of the temperature field, airflow velocity field in the typical position. The results indicated that average temperature of no-PSD system platform is 2.5 ~3 °C higher than that of PSD system, standing room is 1.5 °C higher than that of PSD system, but these also meet the requirement of the standards of the environmental control and passengers’ thermal comfort. Meanwhile, through the comparative analysis to the energy consumption of the two systems, we find ventilating condition has superior to PSD system in energy saving, and it is more suitable for the local climate in the northeast. |